Hi everybody,
I would like to meter a 3-phase connection (3x 230v + N). I have 3 x 50A clamps, each connected to one of the 3 phases. On the Flukso the three clamps are set up as 3 phase configuration, ports 1, 2, 3.
However the Dashboard is not showing any data at all. The heartbeat is registered correctly, under sensors I can see all three clamps, the flukso ping is successful.
I have no idea what else to try...?
Any help is greatly appreciated!
Regards,
Tobias
Ref to https://www.flukso.net/content/flukso-not-showing-data-dashboard - does the syslog show pulses?
Mostly a "save" again solves the issue; otherwise see also https://www.google.de/search?q=site:flukso.net+no+dashboard
Thanks Gebhardm,
saving the configuration again (although it took multiple times) made everything working!