USA Sensor Config

Just got my Flukso today in the US. I have two 120V legs. When I initially set it up I configured it as a single phase in the configuration. This showed a value for both legs in the house. So I changed it to a three phase hoping it would total the sensors, but it doesn't seem to be doing that. I am only getting the values for one leg.

What is the proper configuration? Does it need to be set as single and then I manually add them or is there a way to get it to total everything up?

Thanks!!

icarus75's picture

Hi Torey,

Putting the FLM in 3-phase mode will map inputs 1 through 3 onto port number 1. So for two 120V legs, you should select 3-phase mode, enable and configure port 1 and connect the two clamps to inputs 1 and 2. The fact that nothing is connected to port 3 shouldn't matter.

Cheers,
Bart.