Your FLM seems to be working just fine. However, no readings are being registered. So:
1/ Have you connected your clamp to the FLM?
2/ Is the clamp clamped around a single conductor in which a non-zero current is flowing?
inkoop |
We have the same problem.
- The clamp is connected (sensor #1)
- The clamp is clamped around the main power just below the meter.
Sensor #2 and #3 are configured, but not enabled and not connected yet.
Ho to troubleshoot this?
When I try to connect to the FLM via WiFi using port 8080: what login/password should I use?
Thanks
Chiel
bazzle |
It should be clamped on a SINGLE live wire. If there is 2 under the insulation it will cancel out.
bazzle |
For your wifi you need to use the same one you use to connect your PC to wifi.
icarus75 |
Make sure your FLM is connected to the internet when configuring the sensors. And don't forget to press the save button after you've configured all relevant sensors on the sensor page.
Your FLM seems to be working just fine. However, no readings are being registered. So:
1/ Have you connected your clamp to the FLM?
2/ Is the clamp clamped around a single conductor in which a non-zero current is flowing?
We have the same problem.
- The clamp is connected (sensor #1)
- The clamp is clamped around the main power just below the meter.
Sensor #2 and #3 are configured, but not enabled and not connected yet.
Ho to troubleshoot this?
When I try to connect to the FLM via WiFi using port 8080: what login/password should I use?
Thanks
Chiel
It should be clamped on a SINGLE live wire. If there is 2 under the insulation it will cancel out.
For your wifi you need to use the same one you use to connect your PC to wifi.
Make sure your FLM is connected to the internet when configuring the sensors. And don't forget to press the save button after you've configured all relevant sensors on the sensor page.