Hi Community,
I have 3phase 220V system:
situaton - http://goo.gl/HLWA5l
between phases - 400V
I measure 721W with certificate wattmeter, but on fluksometer graph is 1000W.
graph - http://goo.gl/K48zfC
Any recommendations?
Thank you!
Jakub
Hi Community,
I have 3phase 220V system:
situaton - http://goo.gl/HLWA5l
between phases - 400V
I measure 721W with certificate wattmeter, but on fluksometer graph is 1000W.
graph - http://goo.gl/K48zfC
Any recommendations?
Thank you!
Jakub
Make sure that the clamps are tightly closed; any air gap of the ferrit in the clamp head will influence the readings. The clamp installation as such looks common, so no issue there.
Thanks, but all clamps are tightly closed.
Can you change the voltage constant in setup page for sensor to adj erroe.
Thanks,
i made some tests.
My Rack input - 775W
Flukso without any clamps - 42W on flukso.net graph
220V in fluksometer seting - 1020W on flukso.net graph
184V in fluksometer setting - 780W on flukso.net graph
http://goo.gl/hraZ4l
Is this normal workaround?
J.
Yes , can be for current clamps.
Pulse meters you adjust the constants. (din rail meter)
Ok, thanks!