Missing Data on Graph

Installed my new fluksometer last night and mains consumption has been monitoring AOK. Now the sun is out the solar pv generation should be appearing but it's not.

I have connected via the LAN port and can see the gauge is measuring AOK, so it just appears not to be reporting to the flukso servers and/graphing correctly?

Thanks

AttachmentSize
gauges.png42.43 KB
graph.png49.04 KB
ltickett's picture

2 weeks have passed and still no answer. rather disappointed having now shelled out probably in the region of £500. does anyone have any suggestions?

gebhardm's picture

Would you be so kind to repeat your question? Your graphs look rather OK, so probably nobody got the issue you try to file?! How are the clamps connected within the overall wiring? Note that mains with incoming and outgoing feed make it impossible to differentiate - see https://energyhacks.wordpress.com/2014/07/10/wire-to-measure/

gebhardm's picture

...and what is the parameterization you chose in the setup? With a little more information you probably get a larger chance of a reaction (your single solar graph indeed looks a "bit low"). You claim local gauges are correct. Have you resynched (saved you parameters again)?

ltickett's picture

Wow, so it appears the current clamps can tell the direction the current is flowing! I did not know this was possible.

I figured this out because my mains graph goes to zero when the sun shines (I expected it to report a positive value even when it was negative).

I rotated the solar current clamp 180 degrees and it now appears to be graphing!

I will keep you posted.
Thanks