Hello,

is there any way to share your usage to a non-flukso-member? I want someone else to view the usage of my flukso, without the need of logging in etc.

Thanks

3 wire 3 phase monitor with two or three CT's?

Hi, have Just installed my flukso v2, it's been running for about 24 hours now :

Second major question,

System is as described below, when I first setup I selected 3 phase in the sensor setup, with a reduced voltage as suggested by Bart in another post. However this yielded very high 10kw load for a consumer that I know is rated at 4kva.

When I spilt the three phases out I see approximately correct wattages per phase

This lead me to do a bit of reading around and I came across this document

https://www.ohiosemitronics.com/pdf/tech_papers/Two-wattmeter-method(E).pdf

3 wire 3 phase monitor with two or three CT's?

Hi, have Just installed my flukso v2, it's been running for about 24 hours now :

Second major question,

System is as described below, when I first setup I selected 3 phase in the sensor setup, with a reduced voltage as suggested by Bart in another post. However this yielded very high 10kw load for a consumer that I know is rated at 4kva.

When I spilt the three phases out I see approximately correct wattages per phase

This lead me to do a bit of reading around and I came across this document

https://www.ohiosemitronics.com/pdf/tech_papers/Two-wattmeter-method(E).pdf

Daily graphs showing approx twice the peak watts of hourly graphs

Hi, have Just installed my flukso v2, it's been running for about 24 hours now :

First major question, the peak wattages on the daily and hourly graphs are significantly different,

The daily graph is showing peaks approximately half the level of the hourly graphs. 4kw hourly vs 2kw daily.

Are there any possible explanations for this ?

Regards Keith.

System is Belgian and setup is as follows :

3 phase 3 wire unbalanced both single phase ( line to line ) and three phase mixed inductive and restive loads
Line to line voltage is 220v Line to earth voltage 128v

Direction of the clamp instalation.

Dear, let me check something with you, is the direction of the way clamp is installed on the power cable relevant? I was sure it was not. But from the measurements of the very same cable with 3 clamps I now see that the clamps have to be installed in one direction in order give the same results.

When opened the clamp has K and L leters printed on the inside. If K is toward the power plant and L toward the 100W bulb it gives probable 93-95W readout, if I connect the clamp other way round it will only show 79-80W.