3 wire 3 phase monitor with two or three CT's?
by
onHi, have Just installed my flukso v2, it's been running for about 24 hours now :
Second major question,
System is as described below, when I first setup I selected 3 phase in the sensor setup, with a reduced voltage as suggested by Bart in another post. However this yielded very high 10kw load for a consumer that I know is rated at 4kva.
When I spilt the three phases out I see approximately correct wattages per phase
This lead me to do a bit of reading around and I came across this document
https://www.ohiosemitronics.com/pdf/tech_papers/Two-wattmeter-method(E).pdf